Repair Related Issues

FAQ
What should I do if the generator can't start?
What is the reason why the unit cannot start? You can contact us directly, our company will have professional personnel to solve the problem for you.
Why can't the generator stop?
The unit cannot be shut down. It may be due to mechanical factors or human factors. Due to the difference in the design, type and control system of the unit, you need to know what is the cause. You can contact us directly, and our company will have professional personnel to provide you solve the problem.

The following table shows the simple troubleshooting methods for general unit failures:

failure situation possible reason Solution
1. The engine cannot be started or is difficult to start Insufficient battery voltage Check whether the battery fluid is sufficient and whether the automatic charger works
Daily fuel tank switch not turned on Turn on the switch and drain the air in the oil line
There is air in the diesel line Air in the discharge line
Diesel filter clogged change filter
Loose control wiring or open circuit Check wiring
Autostart plate failure replacement or repair
Start subsidy relay failure replace
Starter motor failure Remove for testing or repair
Internal damage to the engine Please check with the original technician
governor failure Please check with the original technician
2. The engine cannot be stopped after starting Autostart plate failure replacement or repair
Loose control wiring or open circuit Check wiring
Engine governor failure Please check with the original technician
Engine stop solenoid switch failure replacement or repair
3. Insufficient engine horsepower Diesel system has air Check the diesel pipeline for leaks and tighten the screws
Diesel filter clogged change filter
Air filter clogged change filter
Diesel fuel is of poor quality or contains moisture replace
Insufficient rated speed (insufficient frequency) Corrected frequency value
Too much engine oil Check the oil and correct it if too much
Load has exceeded engine horsepower reduce load current
Fourth, the engine smoke is not normal Too much engine oil Check the oil and correct it if too much
Engine temperature is too low Wait until the engine temperature rises to normal before loading
Crankcase pressure too high Engine breather net blocked, clear it
load overload reduce load current
Diesel fuel is of poor quality or contains moisture Check and replace
Injector failure or carbon deposition Injector calibration
5. Abnormal engine sound Injector clogged Injector calibration
Incorrect valve clearance Adjust valve clearance
Inlet and exhaust steam leakage After inspection, lock the pipeline
Engine operating temperature is abnormal Check ambient ambient temperature and engine temperature
6. Engine water temperature is too high Insufficient cooling water Check the cooling water in the water tank
There is air in the cooling water pipe Air in the discharge line
Blocked radiator fins Remove debris and wash
Fan belt is broken or not tight enough replace or adjust
Blocked or twisted cooling water lines Update after checking or contact the original factory
Cooling water thermometer malfunction replace
broken fan replace
7. Engine oil pressure is too low Insufficient oil, not up to standard</p Add oil
Oil filter clogged replace
Engine temperature is too high Refer to Failure Scenario 6
Oil pump failure Contact the original factory
Oil pressure gauge failure replace
8. After the generator set is started, there is no AC output Power circuit breaker not turned on Open
AVR failure Contact the original factory
Diode fault in generator head replace
Instrument failure replace
9. The generator set cannot be started after a power failure Engine won't start Refer to failure case 1
The power outage time is too short (fake power outage) The power failure time is too short, and the generator does not start when the engine delay start time is not reached
ATS does not send a signal to start the generator ATS failure, repair
The remote control circuit between ATS and generator set is loose or disconnected Check wiring
10. The alternator is abnormal Voltage is too high Adjust the voltage adjustment knob
Voltage is too low Adjust the voltage adjustment knob
Voltage swing is unstable Adjust the "Stable Adjustment" of AVR
Load current is too high reduce load current
Capacitors on the load side turn off the capacitor
11. Abnormal shutdown of the generator set Low oil pressure shutdown Refer to failure case 5
High water temperature shutdown Refer to Failure Scenario 6
High (low) speed shutdown Check the engine frequency value and correct it
Overload shutdown reduce load current
Overcurrent shutdown reduce load current
High (low) voltage shutdown Refer to Failure Scenario 10
Battery high (low) voltage warning Check the charger and battery

WARNING: Start the machine only when it is safe to do so; do not attempt to start the machine when you know it is unsafe.